Instructions to Start And Stop Diesel Generator Set



5.3Initial start/stop----Automatic start control panel (initial start and stop)

The following procedures are applicable for the initial start of the electric generating set configured with automatic start control system or the first start after a period maintenance of the generating set.






Notice

*Press the emergency button or switch the control switch to STOPto stop the engine at any time.

*Before restart, release the emergency stop button and rotate clockwise. Meanwhile, switch the control switch manually to STOP.

1. Examine before start the machine according to Chapter 5.2
2. Connect battery to the engine, first positive electrode and then load.
3. Check whether the engine oil is filled to the assigned level.
4. Check whether water is filled.
5. Discharge the air in fuel system.

Connect and start the abnormal fueling system will cause unburned oil accumulated in the smoke evacuation system, bringing potential explosion risk.

4.Fill the fuel supply system with manual fuel tank and discharge the air accumulated in the oil filter. (For more detail information, please refer to the Diesel Manual)

StartPut the main controller to start position manually and press the start button. The diesel will automatically start for three times until started. If failed to start, the control system will lock at starting failurewhile the fault indicator on the control panel will be on. Under this condition, please refer to the Diesel Manualto find out the reason of starting failure.

If failed to start for many times, dismount the connector of the smoke evacuation pipe to disperse the unburned oil gas. Once the oil gas (white smog) dispersed and other faults for starting failure are rejected, reinstall the exhaust pipe and restart.

6Check whether theres unusual noise or vibration.

7Check the cooling liquid and smoke evacuation system for leakage.

8. Check the control panel indicator lights for abnormality, especially for unusual high temperature or extremely low oil pressure. The oil pressure shall be in normal range 10s after the starting.

9Check the voltage and frequency displayed on control panel. Voltage is the indicating rated voltage set by the factory and the load frequency of generating set with 50 cyclic waves is about 52 cyclic waves and 62 cyclic waves for generating set with 60 cyclic waves. (Electronic governor or cyclic wave of EFI unit can be pre-set an ideal value close to the rated cyclic wave.) There are three ways for voltage adjustment: if the control panel installed with voltage adjustment potentiometer, voltage can be adjusted through it; fine adjustment can be achieved through a potentiometer installed in the automatic voltage adjuster in the terminal box of alternator; output voltage alternation requires to change the coil of alternator with the coil joint stored in the terminal box.

For more information on connection, please refer to the Alternator Manual.

Cutoff switch is not allowed to switch on during the phase examination.

10When the electric generator already produced voltage, install the phase meter on one side of the cut off switch of the generator for phase examination, which shall be implemented by qualified technicians.

11Stop machineIf  press the emergency stop button, the machine will stop running immediately. If press the manual stop button, the machine will stop according to the set procedures.

12Check the remote control device, release the emergency stop button and put the controller on AUTOInput the remote control signal and the engine will start according to the abovementioned procedures. Clear the remote control signal and the engine will stop immediately.

NoticeWhen receive stop order, control system will control the engine to run continuously for a while depending on the cooling time before the automatic stop for the purpose of cooling.

13Now the load cable can be connected and the generator is ready for normal operation.

5.4Normal manual start / stop------Automatic start control panel (normal start and stop)

Notice

* Press the emergency stop button and the generator will stop at any time.

* The emergency stop button shall be reset by clockwise rotation before restart.
1Examine before start according to the description in Chapter 5.2.
Notice

* It is not allowed to start the machine when the fault indicator light is on. Turn

off the controller again and reconnect to the power switch for entering into a start procedure. Make sure all faults cleared before start.

2Manual start: Make sure the emergency stop button reset. Put the manual button of controller to manual position and press the start button, releasing it when the indicator light above the start button is on. At this moment, controller enters into starting procedure and diesel will automatic start for 3 times until started. If the diesel failed to start, controller will display starting failureand fault indicator light on the control panel will be on. Under this condition, please refer to the 9th section to find out the fault or refer to refer to the Diesel Manualto find out the reason of starting failure.

The unburned oil gas accumulated in the smoke evacuation pipe caused by many times starting failures is of explosive danger. Therefore, first disconnect the joint or pipe of the exhaust pipeline to let the white oil smog disperse, and find out the starting failure faults, and then reinstall the exhaust pipeline for restart.





Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...