The Reason of generator faults alarms

Diesel generator set is a power generation equipment, it uses diesel oil, driven by a diesel engine to generate electricity. The whole set of diesel generator is generally composed of diesel engine, generator, control cabinet, fuel tank, storage battery for starting and control, protection device, emergency cabinet and other components.

The alarm function of the diesel generator set will automatically start and sound when the diesel generator has the following conditions:
1.Over speed.
2.High water temperature in water tank.
3.Low oil pressure.
4.Over current display on the control panel.
5.Over voltage.
6.When other abnormal phenomena occur, the alarm function of diesel generator set starts or the self-protection function of diesel generator plays a role.

 Diesel generator

What is the reason of faults for low voltage shutdown?
1.Mechanical speed regulation of diesel engine
Diesel engine speed regulation includes electronic speed regulation and mechanical speed regulation. If it is mechanical speed regulation, there is an oil pump mechanism on the diesel engine to control the oil volume and oil circuit, it seems called common rail oil pump. There is a pull rod on it to control the oil quantity. It is called speed regulating pull rod temporarily. A speed limiting (high-speed) top rod and speed regulating top rod are distributed on both sides of the speed regulating pull rod, and the low pressure will be reported after starting and running for 20s. If the voltage and frequency is still not in normal value, the reason may be speed. We can try to adjust regulation top rod. If diesel genset has faults, there must be a main fault. After resolving the main fault, all problems will be resolved.

2.Voltage sample line loose
If the line is loose, there will be no voltage.
3.Residual magnetism
If the generator has no residual magnetism, the voltage system of the generator cannot be built at the beginning. For this problem, we need to know how much voltage the excitation output of the AVR regulator plate of the generator is, and then connect the corresponding voltage source on the excitation output line for magnetization (the voltage type should be corresponding, and the polarity should not be reversed).

4.Grounding fault
If the outgoing line is three-phase grounded, the voltage and current are very low. At this time, it is mainly to check whether the grounding discharge device (such as the grounding knife) is closed or grounded.

5.Regulating plate fault
Due to the change of environmental factors, the parameters of AVR pressure regulating plate are no longer applicable and need to be readjusted. Generally speaking, this kind of problem will not appear in non parallel diesel gensets. Because the parameters of the pressure regulating plate are fixed value (400V), we can't adjust them generally. Only the unit used for parallel operation may have this problem. Because AVR voltage regulator is regulated according to the voltage of main bus during parallel operation, it is not unchangeable. At this time, there is a voltage regulating signal sent to AVR voltage regulator by parallel operation device. In this case, either check whether the voltage regulating signal is connected wrongly or try to use electronic control (parallel operation device, voltage regulator, etc.) to readjust the voltage quickly when starting up.

6.The varistor or rectifier bridge diode on the generator winding is damaged
The function of varistor is to turn on the varistor in case of over-voltage fault to reduce voltage. If the varistor is broken down or turned on for other reasons, it can be imagined that the voltage must be very low. The rectifier bridge has 6 diodes. The set DC power supply is used to supply the regulator and excitation devices. If the rectifier bridge diodes are damaged, the function of the regulator and excitation devices will be greatly weakened buckle.

Hope above information is helpful to you. We also supply whole set of diesel generators, we have our own factory in Jiangsu China since 1974. If you are looking for diesel generators, please contact us by email sales@dieselgeneratortech.com, we will work with you.

Comments

Popular posts from this blog

Components of Cummins PT Fuel System

When it comes to Cummins generator, it is well known that the gensets have good quality, low fuel consumption, low noise, big output power and reliable performance. The reliable stability, economy, power performance, durability and environmental safety is welcomed by customers. In last article, we talk about CCEC Cummins diesel engines operating principles. Well, in this article, you will learn what are the major components of its PT Fuel System. Fuel System The PT fuel system is used exclusively on Cummins Diesels. The identifying letters, “ PT ” are an abbreviation for “ pressure-time ” . The operation of the Cummins PT Fuel System is based on the principle that the volume of liquid flow is proportionate to the fluid pressure, the time allowed to flow and the passage size through which the liquid flows. To apply this simple principle to the Cummins PT Fuel System , it is necessary to provide: 1. A fuel pump. 2. A means of controlling pressure of

Leroy-Somer Alternator AVR R450

1 - GENERAL INFORMATION of Leroy-Somer Alternator AVR R450 1.1 - Description The R450 AVR is supplied in a casing designed to be mounted on a panel with dampers. - Operating temperature: - 30°C to + 65°C. - Storage temperature: - 55°C to + 85°C. - Shocks on the base: 9 g depending on the 3 axes. - Vibrations: less than 10 Hz, 2 mm half-peak amplitude 10 Hz to 100 Hz: 100 mm/s, above 100 Hz: 8 g. The AVR is IP00, it must be incorporated in an environment which ensures it a IP20 protection. 1.2 - Characteristic The connection is realised by “Faston” connectors and the voltage sensing is single - phase. 2 - POWER SUPPLY Both the SHUNT/AREP & PMG excitation systems are controlled by the AVR. 2.1 - AREP excitation system With AREP excitation, the electronic AVR is powered by two auxiliary windings which are independent of the voltage sensing circuit. The first winding has a voltage proportional to the   alternator   main voltage (Shunt characteristic),

New Yuchai engine YC6K600-D30 power for diesel generator 50Hz