Available Control Functions of Volvo Engine


Available Control Functions of Volvo Engine


There are other possibilities than the VP status/pedal position message in order to control the Volvo engine speed. Torque speed control - TSC1 (0C 00 00 03/11/E6) The TSC1 message has priority over the pedal position that is sent with the VP status message. With the TSC1 message with source address 0x03, 0x11, 0xE6, the engine speed and torque can be continuously controlled.



With the TSC1 message with the source address 0x11 it is possible to limit the available torque or speed from the Volvo engine.



P0013959.jpg



Figure 4: The yellow graph shows the available engine torque when the TSC1 signal sets to 80% in the torque limiting factor.

The picture shows an example on how an engine would react when limiting the torque via the TSC1 message.



Start battery test

Whit the fuel disable request in the VP status message, it is possible to perform a start battery test.



Special requirements with EATS

The engines equipped with exhaust after treatment systems have some more requirements regarding which messages that includes error code information.

DEF level

The DEF level is broadcasted on the J1939 bus via

SPN 1761. SPN 1761 will show a value between 0 - 100%

DEF level diagnostics

The DEF level diagnostics are sent via two different SPN numbers. These SPN numbers are SPN 5245 and 5246 and they are included in the message AT1TI (PGN 65110). See table 5 for location of these signals in AT1TI.



There are different inducement levels to motivate the operator to not use the engine when the EATS does not work properly. The inducement level active is communicated via SPN 5246 as described in table 7.

  

EMS-2 extra stop

On EMS2 engines the extra stop is level triggered as shown in figure 7. The default setting is Energized to stopwhich means that when there is power on this pin the engine will stop and it will not be able to start until the stop signal is deactivated.

If the parameter Stop function EMS, energized tois set to run, there needs to be battery power on this pin in order for the engine to be able to run.



 Figure 7 The extra stop functionallety on EMS2 engines..jpg

Figure 7: The extra stop functionallety on EMS2 engines.





Diagnostic Function

The diagnostic function monitors and controls that the EMS system functions normally. The diagnostic function has the following tasks:

Detecting and locating disturbances

Reporting detection of disturbances

Providing guidance when fault tracing

NOTICE! With the DCU:n it is possible choose the language that the information is presented in.

If the diagnostic function detects a disturbance in the system, this is reported using fault codes via the instruments.

Both active (unrectified) and passive (rectified) faults are stored in the control unit.

Refer to the Operationheading for reading fault codes/fault messages.

All fault codes and fault messages are found in the fault code list, with information about the reason, reaction and measures to be taken. Refer to Fault Code Register.





NOTICE! All instruments are optional.

Effect on engine

Engines are affected differently, depending on the severity of the fault discovered by the diagnostic function.

A fault message in the form of a fault code is always generated when a malfunction is discovered by the diagnostic function.

Engines are affected differently, depending on the severity of the fault:

The engine is not affected

Engine goes to idle

Engine torque is restricted to a certain amount

Engine is stopped



Active and Inactive Faults

Active faults

At the same time, the fault is stored in the control unit memory. When the fault has been attended to and the ignition is switched off and on again, the fault disappears as active.

DCU (Display Control Unit)

text !! ENGINE WARNING !! shown on the display.

CIU (Control Interface Unit the diagnostic lamp starts to flash.

• ”Easy Linkinstrument- the relevant lamp on the alarm panel lights up- after the diagnostic button has been pressed, the fault code is shown as text on the tachometer display.





Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...