Tips for Volvo Diesel Engine Maintenance
According to Marketing Department of the Italy-based Visa SpA one of the world’s leading gensets suppliers, dedicated to design, production, sales and rental of generating sets; some engines used in Stand-by generating set applications have had a few issues concerning diesel fuel.
“While the engine maintains its mechanical properties, it can give rise to problems related to the quality of diesel fuel. The chemical make-up of diesel fuel has changed in recent years; a certain percentage of biodiesel at low or high temperatures releases impurities, while a certain percentage of biodiesel at warm temperatures mixed with water (condensation) can be the cradle of bacterial proliferation. Besides, the reduction of Sulphur reduces lubrication, which eventually blocks the fuel-injection pumps.”
“Moreover, by purchasing a genset, it is important to know that a wide range of optional accessories are available that allow to extend maintenance intervals and ensure providing quality power throughout the genset’s life. In the mobile range for example, Visa SpA offers fuel water separator filters, giving the customers the reassurance required when engine failure is not an option, or the fuel tank inspection points.”
Ms. Clarizza Cortez of Adpower one of the leading providers of Diesel and Gas Generators in the Middle East and North Africa also mentions that, since the fuel quality is bad in most countries, they install Water Separator Fuel Filters and additional filtration system to protect the sensitive fuel injection system; and advise the customers to replace the elements on time to avoid such breakdowns.
Testing Batteries
Weak or undercharged starting batteries are a common cause of standby power system failures. The battery must be kept fully charged and well-maintained to avoid dwindling by regular testing and inspection to know the current status of the battery and avoid any start-up hitches of the generator. They must also be cleaned; and the specific gravity and electrolyte levels of the battery checked frequently.
• Testing batteries: Merely checking the output voltage of the batteries is not indicative of their ability to deliver adequate starting power. As batteries age, their internal resistance to current flow goes up, and the only accurate measure of terminal voltage must be done under load. On some generators, this indicative test is performed automatically each time the generator is started. On other generator sets, use a manual battery load tester to attest the condition of each starting battery.
• Cleaning batteries: Keep the batteries clean by wiping them with a damp cloth whenever dirt appears excessive. If corrosion is present around the terminals, remove the battery cables and wash the terminals with a solution of baking soda and water (¼ lb baking soda to 1 quart of water). Be careful to prevent the solution from entering the battery cells, and flush the batteries with clean water when finished. After replacing the connections, coat the terminals with a light application of petroleum jelly.
• Checking specific gravity: In open-cell lead-acid batteries, use a battery hydrometer to check the specific gravity of the electrolyte in each battery cell. A fully charged battery will have a specific gravity of 1.260. Charge the battery if the specific gravity reading is below 1.215.
• Checking electrolyte level: In open-cell lead-acid batteries, verify the level of the electrolyte at least every 200 hr of operation. If low, fill the battery cells to the bottom of the filler neck with distilled water.
5.Routine Engine Exercise
Regular exercising keeps the Volvo diesel engine parts lubricated and thwart oxidation of electrical contacts, uses up fuel before it deteriorate, and helps to provide reliable engine starting. Engine exercise is recommended to be executed at least once a month for a minimum of 30 min. loaded to no less than one-third of the nameplate rating.
Most importantly, when it comes to engine maintenance, according to Peter Whitfield of YorPower a leading independent UK diesel generator manufacturer, it is recommended to do inspections regularly because preventative maintenance is better than reactive maintenance. Nevertheless it is of utmost importance to follow the designated service procedure and intervals.
Keep your Diesel Generator Clean
Oil drips and other issues are easy to spot and take care of when the engine is nice and clean. Visual inspection can guarantee that hoses and belts are in good condition. Frequent checks can keep wasps and other nuisances from nesting in your equipment.
The more a generator is used and relied on, the more it needs to be taken care of. However, a generator set that is rarely used might not need a lot of care.
Exhaust system inspection
In case there are leaks along the exhaust line which usually occurs at the connection points, the welds and the gaskets; they should be repaired immediately by a qualified technician.
Comments
Post a Comment