How to disassembly and insect fuel injector of 300kw diesel genset



For fuel injector of 300kw diesel generator with long time use, if we want to check whether it is normal, can test it spray test on test-bed. If it is found that the follows situations, we need to disassemble and inspect:
Opening pressure of fuel injection is lower than the specified value and the fuel is not atomized.
No obvious cutting or oil dripping.
Nozzle blockage.
The spray of oil mist from four spray holes is uneven, with different lengths.
Serious carbon deposit at the head of fuel injector.

How to disassemble fuel injector of 300kw diesel generator?
Firstly, loosen the pressure regulating nut and screw out the pressure regulating screw. Secondly, clamp the fuel injector upside down in the vise to loosen the fuel injector tightening cap. Then, disassemble other parts and clean it by clean diesel oil.
The carbon deposit at the nozzle head can be removed with a copper wire brush. If the needle valve is bite, clamp the end of the needle valve with the wire clamp pad interface, and pull out with slight rotation and force. The dirt on the needle valve cone shall be removed along the surface of the copper wire brush. And use a drill or steel wire with corresponding size to dredge the oil injection hole and oil path. Finally, put the fuel injection nozzle assembly in diesel oil and pull the needle valve back and forth for cleaning, until the needle valve can slide freely.


After clean injector parts of 300kw diesel generator set, if find the follow abnormal situations, we should repair or replace:
1.When the end face of the injector body combined with the needle valve body is slightly damaged, it can be grinded on the grinding plate after pulling out two locating pins. Pay attention not to touch the end face when pulling out the locating pin.
2.If face of injector pressure regulating spring is damaged, when pitting or permanent deformation occurs, we should replace.
3.Carbon deposits on the inner shoulder blades and hole wall of the tight cap of the splasher shall be completely removed.
4.If the diameter of the nozzle coupling is worn, and if serious oil leakage, it should be replaced.
5.When the spray hole has defects such as wear and increase, and affecting spray quality, we should replaced it.
6.When the wear of sealing seat surface of needle valve and needle valve body is not serious, aluminum oxide grinding paste can be used for mutual grinding and repair. During mutual lapping, do not use too much force, and the sealing surface can reach a uniform and not too wide sealing belt.
7.Because the gas in the cylinder of diesel engine flows back or small impurities enter into the nozzle, causing needle valve black or stuck, it can be reused or replaced depending on the severity after cleaning and mutual study.

The following points should be paid attention to when assembling the fuel injector of 300 kW  diesel generator set:
1.During the assembly, parts must be kept clean. In particular, the sealing parts of the fuel injector couple and the end face of the fuel injector body of the 300kW diesel generator set. Even the small debris and dust will cause the sliding block of the couple and poor sealing of the contact surface.
2.The shoulder blade surface between the tight cap of the injector and the nozzle shall be smooth and smooth without carbon deposit or burr. Otherwise, it will affect the coaxiality and perpendicularity of the installation of the fuel injection nozzle coupling parts, resulting in poor sliding performance of the fuel injection nozzle.
3.When assembly, first screw in the oil inlet pipe joint with filter element, press the copper washer tightly to ensure no oil leakage. Then place the pressure regulating spring and ejector pin into the fuel injector, screw in pressure regulating screw, until the pressure regulating spring is just contacted, then screw on the adjusting nut.
4.Clamp the fuel injector of 300 kW diesel generator set on the vise, tighten the tight cap, its tightening torque is 59 ~ 78N·m. Deformation of needle valve body will be caused by excessive torque, which affects the sliding of needle valve. If too small, it will cause oil leakage.
5.The assembled fuel injector assembly should be sealed and sprayed on the test bench. And adjust the injection opening pressure.

Starlight Power is a manufacturer of 20kw-3000kw diesel generator set, if you have purchase plan, welcome to inquire us by email sales@dieselgeneratortech.com, we will work with you.

Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How to know and solve faults of genset voltage transformer

 Today Starlight Power shares the common faults for voltage transformer of diesel generator set. Hope it is helpful to you. 1) The insulation between iron chips is damaged. Fault phenomenon: temperature rises during operation. The possible causes of the failure are: poor insulation between iron chips, bad use of environmental conditions or long-term operation under high temperature, which promote the insulation aging between iron chips. (2) Poor contact between grounding plate and iron core. Fault phenomenon: there is discharge sound between iron core and oil tank during operation. Cause of failure: the grounding plate is not inserted tightly, and the mounting screw is not tightened. (3) The iron core is loose. Fault phenomenon: abnormal vibration or noise during operation. The cause of failure: the iron core clamp is not clamped, and the iron chip is loose. (4) Turn to turn short circuit of winding. Fault phenomenon: during operation, the temperature rises, there is ...