Why the Fuel Injection Pump Does Not Supply Oil

The main reason why the diesel generator set fuel injection pump does not supply oil

1. There is no oil in the fuel tank or the oil switch is not open.
2. The diesel filter is clogged.
3. There is a lot of air in the oil road.
4. The plunger of the fuel injection pump is broken.
5. The plunger couple is excessively worn.
6. The plunger is stuck.
7. The screw groove of the plunger is installed in the wrong position.
8. The oil outlet valve is excessively worn or dirty.
9. The spring of oil outlet valve is broken or the spring force is weakened.
10. The plane contact between the oil outlet valve and the plunger sleeve is not strict, which causes the diesel oil to leak from the gap in the contact surface. The fuel valve is not opened at the top and the fuel injection pump is not supplied with oil.
11. The oil outlet valve is broken.

diesel generator set

Inspection method: If all cylinders do not supply oil, the diesel engine cannot work. If the individual cylinder does not supply oil, the diesel engine is difficult to start, even if started, the work is not stable. After finding this fault, first check if there is oil in the diesel tank, whether the fuel tank switch is open, and whether the vent hole of the fuel tank is blocked. Then unscrew the bleeder screw of the diesel filter and the fuel injection pump, pump the oil with the hand fuel pump or self-flow by the gravity of the diesel fuel. If there is air bubble in the diesel oil flowing out at the bleeder screw, it indicates that there is air in the oil pipeline. It should be found out that the reason is insufficient diesel oil in the fuel tank or the oil pipe joint is loose or the oil pipe is broken and the gaskets are not tight. After troubleshooting, continue to pump oil by hand oil pump or rely on the gravity of diesel to flow freely until there is no air bubble in the diesel oil. Then tighten the bleeder screw and the hand pump.

If the oil is pumped by the hand oil pump or the gravity of the diesel oil flows, it is felt that the oil is not smooth, indicating that the low pressure oil circuit is blocked. Check whether the diesel filter and the low pressure oil circuit are blocked. If there is oil leakage in the low pressure oil circuit, it will also cause the diesel oil to be blocked.
If there is no problem after inspection, the fault is inside the oil pump and should be disassembled and inspected. If there is no problem with the oil pump, the fault is on the fuel injection pump.

For the combined fuel injection pump, the side cover of the fuel injection pump can be removed here, the throttle handle is placed at the stop oil supply position, and the plunger spring seat of the fuel injection pump is pried by the screwdriver to perform the pump oil action, check whether the plunger spring is broken and whether the plunger is stuck.
At the same time, it should also check whether the screw that adjusts the ring gear is loose, resulting in changes in oil supply. If the inspection is good, check the wear degree of the plunger couple and the sealing of the oil outlet valve.

The main reason for the low fuel supply of fuel injection pump of diesel generator set

1. There is air in the fuel injection pump or oil pipe joint is loose and leaking oil.
2. The oil pressure is too low.
3. The oil supply amount adjusted by the plunger is too small, or the loosening of the locking screw of the ring gear is adjusted, so that the oil supply amount is too small.
4. The plunger couple is excessively worn.
5. The oil outlet valve is not tightly sealed.
6. The adjustment screw for limiting the maximum oil amount of the rack in the governor is too small or the throttle handle limit screw adjustment is too small.

Inspection method: After this fault is found, first check whether there is air in the fuel system and whether the oil pipe joint is loose and leaking. If there are no problems in these aspects, check whether the diesel/fuel filter and the low-pressure oil circuit are blocked; the oil supply of the fuel pump; whether the spring of the oil return valve is too weak. After inspection, all are good, the side cover of the fuel injection pump can be removed, check whether the locking screw of the adjusting ring gear is loose and displaced, or the adjusted oil supply is too small. If there is no such phenomenon, check the seal of the oil valve, the degree of wear of the plunger, the maximum oil adjustment screw and the throttle handle limit screw.

The above is the reason and inspection method for the diesel generator set fuel injection pump that does not supply oil or the amount of oil supply is too small. Starlight Power is specialized in the production of diesel generator sets, including Cummins generator set, Volvo generator set, Perkins generator set, etc., and is also one of leading manufacturers of diesel generators in China. Contact us to get the latest price of various brands of generators.

Comments

Popular posts from this blog

Yuchai Is Super Confident in Its Innovation

Founded in 1951, with 30 wholly-owned, holding and joint-stock subsidiaries, Guangxi Yuchai Machinery Group Co., Ltd. (hereinafter referred to as the Yuchai Group) is an internal combustion engine manufacturing base with the most complete spectrum of products in the country. In recent years, machinery manufacturing industry has been dropped off influenced by domestic and foreign economic situations, especially domestic overcapacity and unreasonable product structure. Reversely, Yuchai has sold over 3 million engines with the annualized revenues amount to RMB 40 billion. Over the years, as China ’ s largest engine R&D manufacturing base, Yuchai adjusts and optimizes its industrial structure and constantly strengthens its capacity for independent innovation. Therefore, the key technology continues to be the top in the sector for further keeping its own top leader in the industry. Innovation-Driven In 2013, seven world-class diesel-engine products for high-s...

How to Read Alarm Codes From SmartGen Genset Controller

Auto Module Control Panel is the configuration for nobody on duty controlling generators. This kind of panel adopts auto module control system, with large LCD display to show the menu, such as SmartGen controller. Features:   1. SmartGen 6110 can receive remote output signal from ATS and realize auto start and stop of generators. 2. SmartGen 6310 can realize all functions of 6110, add RS232 interface which can communicate with PC to realize remote operation.  3. SmartGen 6410 Auto Mains Failure controller, can realize all functions of 6310, furthermore can detect  ATS and control directly. The alarm of diesel generator controller is not the amount of stop alarm, which does not affect the normal operation of diesel generator. When the alarm occurs, the unit will not stop, and when the alarm conditions do not exist, the amount of warning will automatically disappear.  Today Starlight manufacturer mainly shares alarm codes for diesel generato...

How Do You Check Diesel Consumption In The Diesel Generator Set?

  Diesel generator sets   are crucial assets in various industries, providing backup power during outages or serving as primary power sources in remote locations. With fuel costs being a significant operational expense, monitoring diesel consumption becomes essential for efficiency and cost-effectiveness. Here's a comprehensive guide on how to effectively check diesel consumption in a generator set. Understanding Diesel Consumption Metrics Before delving into the monitoring process, it's crucial to grasp the key metrics associated with diesel consumption: Fuel Consumption Rate: This indicates the rate at which diesel is being consumed by the generator set, typically measured in liters per hour (L/hr) or gallons per hour (GPH). Load Factor: The percentage of the generator's maximum capacity being utilized at any given time. It directly influences fuel consumption, with higher loads resulting in increased fuel usage. Fuel Efficiency: A measure of how effectively the generator...